What does a lift flex carry?

A lift flex is also called a trailing cable or travelling cable. Many lifts use a flat cable with several conductors side by side inside one flexible sheath. Round travelling cables are used on some lifts too.

The cable carries electrical power and signals between equipment on the car and the fixed installation. The circuits it carries depend on the lift design. Typical examples include:

  • Floor button requests and signals to the display inside the car.
  • Power or control signals for the car door operator, plus signals that report its status.
  • Supplies for car lighting and ventilation.
  • Alarm or intercom connections and, on some lifts, data for displays or CCTV.

Some lifts use dedicated conductors for individual signals. Others send multiple signals over a shared data connection between electronics on the car and the lift controller.

Two common ways to connect the car

Both layouts use a moving loop between the shaft and car. The difference is where the flexible cable ends and the connections continue to the controller.

One continuous flex

The cable continues from the lift car to the control panel. A hanger partway up the shaft can support it without an electrical connection at that point.

Solid line: one continuous cable, supported at the shaft hanger.

Flex via a halfway box

The flex connects the car to a fixed junction box in the shaft. Separate fixed wiring runs from that box to the control panel or motor room.

Dashed line: fixed wiring. Solid line: travelling flex.

Simplified views. The panel and shaft connection can be in different positions on different lifts.

Why does the cable hang in a loop?

One side of the travelling loop is supported by the shaft and the other is carried by the car. As the car moves, the bottom of the U-shaped loop rises or falls. The cable bends through the loop while staying connected at both ends.

Watch the travelling loop

In this simplified layout, the bend moves half as far as the car. As one straight section lengthens, the other shortens by the same amount.

Travelling flex

The flat profile can make it easier to route the cable where space is limited. The cable, supports and clearances must suit the installation and the distance the car travels. Unlike the suspension ropes or belts on a traction lift, the trailing cable carries electrical connections and does not support the car.

What happens when a lift flex develops a fault?

A cable can wear where it rubs against surrounding equipment. Individual conductors can also break inside the sheath after repeated bending. A circuit may work in one car position and lose connection in another as the cable changes shape.

Depending on the circuit affected, a fault might interrupt car buttons, indicators, door operation or communications. A fault that repeats at a certain floor or height is a useful clue. Connectors, car wiring and the control system can produce similar symptoms, so an engineer needs to trace the fault before recommending replacement.

If the fault occurs during normal use, note the floor or direction of travel, what stopped working and any message shown. Send those details and any recent engineer’s report to your lift company. Leave shaft access and cable checks to a lift engineer.

See how we investigate recurring lift faults.

Technical references